Fall per metre for common gradients

GradientFall per metreAs a percentageAs an angle
1 in 2050 mm5%2.86°
1 in 4025 mm2.50%1.43°
1 in 6016.7 mm1.67%0.95°
1 in 8012.5 mm1.25%0.72°
1 in 10010 mm1%0.57°
1 in 1506.7 mm0.67%0.38°
1 in 2005 mm0.50%0.29°

The bigger the second number, the flatter the pipe. To turn a percentage into "1 in X", divide 100 by it: 1.25% is 100 ÷ 1.25 = 1 in 80. Pipe lasers are usually set as a percentage, so 1 in 40 is 2.5% and 1 in 80 is 1.25%.

Fall over a whole run

Run length1 in 401 in 601 in 801 in 150
1 m25 mm17 mm12 mm7 mm
2 m50 mm33 mm25 mm13 mm
3 m75 mm50 mm38 mm20 mm
5 m125 mm83 mm62 mm33 mm
10 m250 mm167 mm125 mm67 mm
15 m375 mm250 mm188 mm100 mm
20 m500 mm333 mm250 mm133 mm
30 m750 mm500 mm375 mm200 mm

Fall over a run = length in mm ÷ X. For anything not in the table, the free Drainage Fall Calculator chains runs together from a starting invert level and gives the level at every manhole.

Working out the gradient from two levels

Gradient (1 in X) = run length ÷ difference in invert levels, both in the same units. Use the inverts (the inside bottom of the pipe), not the cover levels.

Value
Invert at MH198.450 m
Invert at MH298.210 m
Difference0.240 m
Run length18 m
Gradient18 ÷ 0.24 = 1 in 75

1 in 75 is steeper than 1 in 80, so this run meets the minimum for a 100 mm drain serving a WC.

UK minimum falls (Approved Document H)

Approved Document H (England) gives these minimum gradients for foul drains, depending on the peak flow and pipe size:

Peak flowPipe sizeMinimum gradientCondition
Less than 1 litre/second75 mm1 in 40
Less than 1 litre/second100 mm1 in 40
More than 1 litre/second75 mm1 in 80No WCs
More than 1 litre/second100 mm1 in 80At least one WC
More than 1 litre/second150 mm1 in 150At least five WCs
  • Plastic 110 mm drain pipe is the 100 mm size in these tables.
  • In practice that means 1 in 40 for a 100 mm drain with no WC, such as a run taking only a sink or shower, and 1 in 80 once a WC discharges into it.
  • Above-ground waste pipes from basins, baths and showers have their own falls, usually somewhere between 18 and 90 mm per metre depending on the pipe size and length; Table 2 of Approved Document H gives them.
  • Scotland and Northern Ireland have their own building regulations with similar guidance. Check with building control for anything unusual.

Setting out the fall on site

  • Pipe laser: set the grade as a percentage (2.5% for 1 in 40, 1.25% for 1 in 80) and check it at the start of each run.
  • Level and straight edge: on a 1 m level, 1 in 40 is 25 mm of packing under the low end, and 1 in 80 is 12.5 mm.
  • Boning rods or a string line: set the two ends at the right inverts, then sight or string between them to check the bedding in between.
  • Check every few metres for dips. A low spot (a back fall) holds water and collects solids, even when the overall fall is right.